§ 16.14.430. Section A5.106.5.3 Electric vehicle (EV) charging for non-residential structures.


Latest version.
  • Section A5.106.5.3 of the California Green Building Standards Code is adopted as mandatory and amended to read:
    A5.106.5.3 Electric Vehicle (EV) Charging for Non-Residential Structures. New non-residential structures shall comply with the following requirements for electric vehicle supply equipment (EVSE). All parking space calculations under this section shall be rounded up to the next full space. The requirements stated in this section are in addition to those contained in Section 5.106.5.3 of the California Green Building Standards Code. In the event of a conflict between this section and Section 5.106.5.3, the more robust EV Charging requirements shall prevail.
    Definitions. For the purposes of this section, the following definitions shall apply:
    (a) Level 2 EVSE. "Level 2 EVSE" shall mean an EVSE capable of charging at 30 amperes or higher at 208 or 240 VAC. An EVSE capable of simultaneously charging at 30 amperes for each of two vehicles shall be counted as two Level 2 EVSE.
    (b) Conduit Only. "Conduit Only" shall mean, at minimum: (1) a panel capable to accommodate a dedicated branch circuit and service capacity to install at least a 208/240V, 50 amperes grounded AC outlet; and (2) raceway or wiring with capacity to accommodate a 100 ampere circuit; terminating in (3) a listed cabinet, box, enclosure, or NEMA receptacle. The raceway shall be installed so that minimal removal of materials is necessary to complete the final installation.
    (c) EVSE-Ready Outlet. "EVSE-Ready Outlet" shall mean, at minimum: (1) a panel capable to accommodate a dedicated branch circuit and service capacity to install at least a 208/240V, 50 amperes grounded AC outlet; (2) a two-pole circuit breaker; (3) raceway with capacity to accommodate a 100-ampere circuit; (4) 50 ampere wiring; terminating in (5) a 50 ampere NEMA receptacle in a covered outlet box.
    (d) EVSE Installed. "EVSE Installed" shall mean an installed Level 2 EVSE.
    A5.106.5.3.5 Non-Residential Structures Other than Hotels. The following standards apply to newly constructed non-residential structures other than hotels.
    (a) In general. The property owner shall provide Conduit Only, EVSE-Ready Outlet, or EVSE Installed for at least 25% of parking spaces, among which at least 5% (and no fewer than one) shall be EVSE Installed.
    (b) Accessible spaces. Projects shall comply with the 2019 California Building Code requirements for accessible electric vehicle parking.
    (c) Minimum total circuit capacity. The property owner shall ensure sufficient circuit capacity, as determined by the Chief Building Official or designee, to support a Level 2 EVSE in every location where Circuit Only, EVSE-Ready Outlet or EVSE Installed is required.
    (d) Location. The EVSE, receptacles, and/or raceway required by this section shall be placed in locations allowing convenient installation of and access to EVSE. Location of EVSE or receptacles shall be consistent with all City guidelines, rules, and regulations.
    (Ord. 5481 § 1 (part), 2019)